Goodrive200L
inverters Function parameters
75
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.35
FDT2
retention
detection
value
Setting range of P08.32: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P08.33: -100.0~100.0%
(FDT1 electrical level)
Setting range of P08.34: 0.00 Hz ~P00.03
(the Max. frequency)
Setting range of P08.35: 0.0~100.0%
(FDT2 electrical level)
5.0%
○
P08.36
Frequency
arrival
detection
value
When the output frequency is among the below
or above range of the set frequency, the
multi-function digital output terminal will output
the signal of “frequency arrival”, see the diagram
below for detailed information:
The setting range:0.00Hz~P00.03
(the Max. frequency)
0.00Hz
○
P08.37
Energy
braking
enable
This parameter is used to control the internal
braking unit.
0:Disable
1:Enable
Note:
Only applied to internal braking unit. After
enabling, the overvoltage stall point will increase
by 20V more than the energy braking point.
0
○
P08.38
Threshold
voltage
After setting the original bus voltage, adjust this
parameter to break the load appropriately. The
380V
voltage:
○