| Optidrive ODP-2 Solar Pump User Guide |
41
www.invertekdrives.com
Par.
Description
Minimum
Maximum
Default
Units
P1-12
Primary Command Source
0
6
0
-
0
Terminal Control
The drive responds directly to signals applied to the control terminals.
1
Keypad control -
uni-directional
The drive can be controlled in the forward direction only using an external or remote
Keypad.
2
Keypad control -
uni-directional
The drive can be controlled in the forward direction only using an external or remote
Keypad.
3
PID Control
The output frequency is controlled by the internal PID controller.
4
Fieldbus Mode
By the selected Fieldbus (Group 5 Parameters) – Excluded BACnet (see option 6).
5
Slave Mode
The drive acts as a Slave to a connected Optidrive operating in Master Mode.
6
BACNet MS/TP Mode
Drive communicates / responds as a slave within a BACnet network.
P1-13
Digital Input Function
0
16
1
-
Defines the function of the digital inputs depending on the control mode setting in P1-12. See section
for
more information.
P1-14
Extended Menu Access
0
30000
0
-
Parameter Access Control. The following settings are applicable:
P1-14 = P2-40 = 101 : Allows access to Extended Parameter Groups 0 – 5
P1-14 = P6-30 = 201 = Allows access to all parameter groups (Intended for experienced users only, usage is not described in this
User Guide).
7
Full P
arameter List