Version 2.04
| Optidrive ODP-2 Solar Pump User Guide |
55
www.invertekdrives.com
Par
Name
Minimum
Maximum
Default
Units
P5-06 Communications Loss Action
0
3
0
-
0
Trip & Coast To Stop
1
Ramp to Stop Then Trip
2
Ramp to Stop Only (No Trip)
3
Run at Preset Speed 4
P5-07 Fieldbus Ramp Control
0
1
0
-
0
Disabled
Ramps are control from internal drive parameters P1-03 and P1-04
1
Enabled
Ramps are controlled directly by the Fieldbus.
P5-08 Fieldbus PDO4 Data Select
0
7
0
-
When using an optional Fieldbus interface, this parameter configures the parameter source for the 4th process data word transferred
from the drive to the network master during cyclic communications:
0
Motor torque
Output power in kW to one decimal place, e.g. 500 = 50.0%.
1
Motor Power
Output power in kW to two decimal places, e.g. 400 = 4.00kW
2
Digital Input Status
Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc
3
Analog Input 2 Signal Level
0 to 1000 = 0 to 100.0%
4
Heatsink Temperature
0 to 100 = 0 to 100°C
5
User Register 1
Can be accessed by PLC program or group 9 parameters
6
User Register 2
Can be accessed by PLC program or group 9 parameters
7
P0-80 value
P0-80 value can be selected by P6-28
P5-09 BACnet Device Instance Number (Low)
0
65535
0
-
P5-10
BACnet Device Instance Number (High)
0
63
0
-
When using BACNet MS/TP, these parameter together allow a unique Device Instance Number to be programmed into the drive.
P5-11
BACnet Maximum Masters
0
127
127
-
Parameter defines the maximum address of any BACnet masters that can exist on the current local MSTP BACnet network.
When the device is polling for the next master in the network it will not poll about the value set in P5-11. For example, if the value is set
to 50 then when the drive finishes communicating and needs to pass control to the next master it will poll up to address 50 looking for a
response before rolling back to address 0.
P5-12
Fieldbus Process Data Output Word 3 Select
0
7
0
-
When using an optional fieldbus interface, this parameter configures the parameter source for the 3rd process data word transferred
from the drive to the network master during cyclic communications.
0
Motor Current
Output current to 1 decimal place, e.g. 100 = 10.0 Amps
1
Power (x.xx kW)
Output power in kW to two decimal places, e.g. 400 = 4.00kW
2
Digital Input Status
Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc
3
Analog Input 2 Signal Level
0 to 1000 = 0 to 100.0%
4
Drive Heatsink Temperature
0 to 100 = 0 to 100°C
5
User Register 1
User Defined Register 1 Value
6
User Register 2
User Defined Register 1 Value
7
P0-80 value
User Selected data value.
P5-13
Fieldbus Ramp Control
0
1
0
-
0
Fieldbus Ramp Control
This option must be selected if the drive acceleration and deceleration ramps are to
be controlled from the fieldbus. P5-07 must also be set to 1 to enable this function.
1
User register 4
The value received by the drive in PDI 4 is transferred to User Register 4. This option
allows the function of the process data word to be defined in Parameter Group 9.
In this case, User Register 4 should not be written to within any PLC function code,
although the value can be read.
9
Extended P
arameters