6.2. Basic Commissioning Procedure
This section provides a short guide to commission the drive for a standard Photovoltaic Pumping Application. Other functions are
configurable but this guide is intended to provide the user with a starting point, for further information please contact your local
Invertek sales partner for detailed support.
It is the responsibility of the system integrator or the installer to ensure that the solar pump solution is suitably sized for the application
requirements including the dimensioning of the Photovoltaic array. The maximum limits of the P2 solar Pump drive are given in the
technical section of this User Guide and are summarised below:
Drives for use with 400V motors can be fed with DC Voltage from 345 to 800Vdc with a recommended VMPP in the area of 565Vdc
Drives for use with 200V motors can be fed with DC Voltage from 185 to 410Vdc with a recommended VMPP in the area of 325Vdc
Please note that the output voltage of the drive will be limited to the DC Voltage divided by the square root of 2 – this could limit the
maximum operational speed of the pump in certain conditions.
Check PV Array
V
MPP
, Voc, P
MP
are suitable
for VFD
Appropriate
fusing and
SPD installed
Basic electrical
checks OK
Corrective
action
Ensure STO not
present – remove
control terminal block
Re-configure PV array
or swap VFD
Apply power to the drive
Set basic parameters
YES
YES
YES
Check rotation
correct
Insert/replace terminal
block – STO present
Run application
Tune
Change
P4-13
YES
NO
NO
NO
NO
6
Quick Star
t Pr
ocedure