3.9. Removing the Terminal Cover
3.9.1. Frame Sizes 2 & 3
ON
OFF
PWR
Terminal Cover
Release Screws
Using a suitable flat blade
screwdriver, rotate retaining
screws indicated by arrows until
the screw slot is vertical.
3.9.2. Frame Size 4
3.9.3. Frame Size 5
3.9.4. Frame Sizes 6 & 7
3.10. Routine Maintenance
The drive should be included within the scheduled maintenance program so that the installation maintains a suitable operating
environment, this should include:
Ambient temperature is at or below that set out in section
Heat sink fans freely rotating and dust free.
The Enclosure in which the drive is installed should be free from dust and condensation; furthermore ventilation fans and air filters
should be checked for correct air flow.
Checks should also be made on all electrical connections, ensuring screw terminals are correctly torqued; and that power cables
have no signs of heat damage.