6. Quick Start Procedure
6.1. Quick Start Process
Step
Action
See Section
Page
1
Identify the Model Type and ratings of your drive
from the model code on the label. In particular
-
Check the voltage rating suits the
incoming supply
verify the VMPP and Voc for
the array
- Check the output current capacity meets or
exceeds the full load current for the intended
motor
- Check the enclosure type is suitable for the
intended mounting location
2.1. Identifying the Drive by Model Number
2.3. Understanding the Rating Label
2.4. Drive model numbers – IP20
2.5. Drive model numbers – IP55
2.6. Drive model numbers – IP66
3.1. General
2
Unpack and check the drive.
Notify the supplier and shipper immediately of any
damage.
3
Ensure correct ambient and environmental conditions
for the drive are met by the proposed mounting
location.
4
Install the drive in a suitable cabinet (IP20 Units),
ensuring suitable cooling air is available.
Mount the drive to the wall or machine (IP55 &
IP66).
3.1. General
3.2. Before Installation
3.4. Mechanical dimensions and weight
3.5. Guidelines for Enclosure mounting (IP20 Units)
3.6. Mounting the Drive – IP20 Units
3.7. Guidelines for mounting (IP55 Units)
3.8. Guidelines for mounting (IP66 Units)
5
Select the correct power and motor cables
according to local wiring regulations or code, noting
the maximum permissible sizes
11.2. Output Power and Current ratings
6
For IT Supply network, or any power supply type
where the phase – earth voltage may exceed
the phase – phase voltage (such as ungrounded
supplies), disconnect the EMC filter before
connecting the supply.
7
Check the supply cable and motor cable for faults or
short circuits.
8
Route the cables
9
Check that the intended motor is suitable for use,
noting any precautions recommended by the supplier
or manufacturer.
4.4. Motor Connection
9.3.2. Working with different motor types
10
Check the motor terminal box for correct Star or
Delta configuration where applicable
4.5. Motor Terminal Box Connections
11
Ensure correct wiring protection is providing, by
installing a suitable circuit breaker or fuses in the
incoming supply line
4.3.3. Fuse / Circuit Breaker Selection
12
Connect the power cables, especially ensuring the
protective earth connection is made
13
Connect the control cables as required for the
application
14
Thoroughly check the installation and wiring
15
Commission the drive parameters