44
| Optidrive ODP-2 Solar Pump User Guide |
Version 2.04
www.invertekdrives.com
8.2. Digital Input Configuration Parameter P1-13
P1-13
*(2)
Local (Hand)
Control
Function
Digital Input 1
(Terminal 2)
Digital Input 2
(Terminal 3)
Digital
Input 3
(Terminal 4)
Analog
Input 1
(Terminal 6)
Analog
Input 2
(Terminal 10)
Notes
0
N/A
All functions User defined in Menu 9 or configured through PLC function in OptiTools studio software suite.
1
*(3)
Analog
Input 2
O: Stop
C: Run/Enable
O: Normal
Operation
C: Preset 1/
PI Set-point 2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
When Input 3 is
Closed:
Speed Reference =
Analog Input 2
Start Command =
Input 1
In PI Mode,
Analog Input 1
must be used for
feedback
2
O: No Function
C: Momentary Start
O: Stop (Disable)
C: Run Permit
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
3
O: Stop
C: Run/Enable
O: Forward
C: Reverse
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
4
O: Stop
C: Run/Enable
O: Fire Mode
*(1)
C: Normal Operation
*(1)
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
5
Preset
Speeds
O: Stop
C: Run/Enable
O: Preset Speed 1
C: Preset Speed 2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Ext Trip
C: Normal
Operation
When Input 3 is
Closed:
Speed Reference
= Preset Speed
1 / 2
Start Command =
Input 1
6
O: No Function
C: Momentary Start
O: Stop (Disable)
C: Run Permit
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Preset 1
C:Preset 2l
7
O: Stop
C: Run/Enable
O: Forward
C: Reverse
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Preset 1
C:Preset 2
8
O: Stop
C: Run / Enable
O: Fire Mode *
(1)
C: Normal Operation
*(1)
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Preset 1
C:Preset 2
9
*(3)
Keypad
Speed
Reference
O: Stop
C: Run / Enable
O: Normal
Operation
C: Preset 1/PI Set-
point 2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
When Input 3 is
Closed:
Speed Reference =
Keypad
Start Command
= Determined by
P2-37
10
*(3)
O: Stop
C: Run/Enable
O: Normal
Operation
C: Preset 1/PI Set-
point 2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Ext Trip
C: Normal
Operation
11
O: No Function
C: Momentary Start
O: Stop (Disable)
C: Run Permit
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
12
O: Stop
C: Run Fwd
O: Forward
C: Reverse
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
13
O: Stop
C: Run Fwd
O: Fire Mode
*(1)
C: Normal Operation
* (1)
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
14
O: Stop
C: Run
O: Forward
C: Reverse
Digital
input 3
Analog
input 1
Analog
input 2
Preset
Speed
Off
Off
Off
Preset Speed 1
On
Off
Off
Preset Speed 2
Off
On
Off
Preset Speed 3
On
On
Off
Preset Speed 4
Off
Off
On
Preset Speed 5
On
Off
On
Preset Speed 6
Off
On
On
Preset Speed 7
On
On
On
Preset Speed 8
15
*(4)
Float Switch
(NO)
O: Stop
C: Enable
O: Stop (delay)
C: Run (delay)
O: AI1 Ref
C: Preset 1
Analog In 1
Analog In 2
For use with a float
switch connected
to DI 2
16
*(4)
Float Switch
(NC)
O: Stop
C: Enable
O: Run (delay)
C: Stop (delay)
O: AI1 Ref
C: Preset 1
Analog In 1
Analog In 2
Notes
*
(1)
: Logic shown is as per the default setting. Fire mode logic can be configured through parameter P8-09.
*
(2)
: Default setting for P1-13 = 1
*
(3)
: When the drive is in PID control (P1-12 = 3) and digital preset reference is selected (P3-05 = 0) then P1-13 can be set to 1, 9, or
10 to allow selection between two independent digital references using digital input 2. Digital preset reference 1 and 2 are set in
P3-06 and P3-15 respectively.
*
(4)
: When P1-13 is set to 15 or 16, the float switch is intended to be connected between T1 (+24V) and T2 (DI 2) with the delay start
and delay stop configured in P6-06 and P6-07 respectively. The drive enable in DI1 is still required for the drive to run.
Note:
“Motor thermistor trip” connection is via analog input 2 and is configured by parameter P2-33 (
P
). The “External trip”
input is no longer utilised for the thermistor input (this is different to the ODP drive and E2 drive).
8
Contr
ol T
erminal Func
tions