3.7. Guidelines for mounting (IP55 Units)
Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in
section
11.1. Environmental on page 65
.
The drive must be mounted vertically, on a suitable flat surface.
The minimum mounting clearances as shown in the table below must be observed.
The mounting site and chosen mountings should be sufficient to support the weight of the drives.
IP55 units do not require mounting inside an electrical control cabinet; however they may be if desired.
Using the drive as a template, or the dimensions shown above, mark the locations required for drilling.
Suitable cable glands to maintain the IP protection of the drive are required. Gland sizes should be selected based on the number
and size of the required connection cables. Drives are supplied with a plain, undrilled gla
Drive Size
X –Above & Below
Y –Either Side
mm
in
mm
in
4
200
7.87
10
0.39
5
200
7.87
10
0.39
6
200
7.87
10
0.39
7
200
7.87
10
0.39
NOTE
Typical drive heat losses are approximately 3% of operating load conditions.
Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times.
3
Mech
anical Installation