14
| Optidrive ODP-2 Solar Pump User Guide |
Version 2.04
www.invertekdrives.com
The enclosure design and layout should ensure that the adequate ventilation paths and clearances are left to allow air to circulate through
the drive heatsink. Invertek Drives recommend the following minimum sizes for drives mounted in non-ventilated metallic enclosures:
Drive Size
X
Above & Below
Y
Either Side
Z
Between
Recommended
airflow
mm
in
mm
in
mm
in
m3/min
CFM
2
75
2.95
10
0.39
46
1.81
0.3
11
3
100
3.94
10
0.39
52
2.05
0.9
31
4
200
7.87
25
0.98
70
2.76
1.7
62
5
200
7.87
25
0.98
70
2.76
2.9
104
6A
200
7.87
25
0.98
70
2.76
6B
200
7.87
25
0.98
70
2.76
8
350
11.81
50
3.94
20
705
NOTE
Dimension Z assumes that the drives are mounted side-by-side with no clearance.
Typical drive heat losses are <3% of operating load conditions.
Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times.
3.6. Mounting the Drive – IP20 Units
IP20 Units are intended for installation within a control cabinet.
When mounting with screws:
o Using the drive as a template, or the dimensions shown above, mark the locations for drilling.
o Ensure that when mounting locations are drilled, the dust from drilling does not enter the drive.
o Mount the drive to the cabinet backplate using suitable M5 mounting screws.
o Position the drive, and tighten the mounting screws securely.
When Din Rail Mounting (Frame Size 2 Only):
o Locate the DIN rail mounting slot on the rear of the drive onto the top of the DIN rail first.
o Press the bottom of the drive onto the DIN rail until the lower clip attaches to the DIN rail.
o If necessary, use a suitable flat blade screw driver to pull the DIN rail clip down to allow the drive to mount securely on the rail.
o To remove the drive from the DIN rail, use a suitable flat blade screwdriver to pull the release tab downwards, and lift the
bottom of the drive away from the rail first.
3
Mech
anical Installation