46
| Optidrive ODP-2 Solar Pump User Guide |
Version 2.04
www.invertekdrives.com
Par
Parameter Name
Minimum
Maximum
Default
Units
P2-12
Analog Output 1 (Terminal 8) Format
See Below
-
= 0 to10V.
= 10 to 0V,
= 0 to 20mA
= 20 to 0mA
= 4 to 20mA
= 20 to 4mA
P2-13
Analog Output 2 (Terminal 11) Function Select
0
11
9
-
Digital Output Mode. Logic 1 = +24V DC
0 : Drive Enabled (Running).
Logic 1 when the Optidrive is enabled (Running).
1: Drive Healthy.
Logic 1 When no Fault condition exists on the drive.
2 : At Target Frequency (Speed).
Logic 1 when the output frequency matches the setpoint frequency.
3 : Output Frequency > 0.0.
Logic 1 when the motor runs above zero speed.
4 : Output Frequency >= Limit.
Logic 1 when the motor speed exceeds the adjustable limit.
5 : Output Current >= Limit.
Logic 1 when the motor current exceeds the adjustable limit.
6 : Motor Torque >= Limit.
Logic when the motor torque exceeds the adjustable limit.
7 : Analog Input 2 Signal Level >= Limit.
Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
Note:
When using settings 4 – 7, parameters P2-19 and P2-20 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-19, and return to Logic 0 when the signal falls below the
value programmed in P2-20.
Analog Output Mode
8 : Output Frequency (Motor Speed).
0 to P-01
9 : Output (Motor) Current.
0 to 200% of P1-08
10 : Motor Torque.
0 to 200% of motor rated torque
11 : Output (Motor) Power.
0 to 150% of drive rated power
12 : PID Output.
Output from the internal PID Controller, 0 – 100%
13: DC Bus Level.
0 – 100.0% = 0 – 1000Vdc
P2-14
Analog Output 2 (Terminal 11) Format
See Below
-
= 0 to10V
= 0 to 20mA
= 4 to 20mA
= 10 to 0V
= 20to 0mA
= 20 to 4mA
P2-15
Relay 1 Function Select
0
11
9
-
Digital Output Mode. Logic 1 = +24V DC
0 : Drive Enabled (Running).
Logic 1 when the Optidrive is enabled (Running).
1: Drive Healthy.
Logic 1 When no Fault condition exists on the drive.
2 : At Target Frequency (Speed).
Logic 1 when the output frequency matches the setpoint frequency.
3 : Output Frequency > 0.0.
Logic 1 when the motor runs above zero speed.
4 : Output Frequency >= Limit.
Logic 1 when the motor speed exceeds the adjustable limit.
5 : Output Current >= Limit.
Logic 1 when the motor current exceeds the adjustable limit.
6 : Motor Torque >= Limit.
Logic when the motor torque exceeds the adjustable limit.
7 : Analog Input 2 Signal Level >= Limit.
Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit.
Note:
When using settings 4 – 7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the
value programmed in P2-17.
8 : Reserved.
No Function.
9 : Reserved.
No Function.
10 : Maintenance Due.
Logic 1 when the internally programmable maintenance timer has elapsed.
11 : Drive Ready.
Logic 1 when drive is not tripped, STO circuit is closed, mains supply present, hardware enable input present.
12 : Drive Tripped.
Logic one when the drive has tripped and the display shows the fault code.
13 : STO Status.
Logic 1 when both STO inputs are present and the drive is able to be operated.
14 : PID Error >= Limit.
The PID Error (difference between setpoint and feedback) is greater than or equal to the programmed limit.
15 : High Load Detection Alarm.
Logic 1 when the load monitoring has been enabled using P8-06 to P8-08 and a high load
condition has been detected – usually used to signal pump blockage.
P2-16
Adjustable Threshold 1 Upper Limit (Analog Output 1
/ Relay Output 1)
P2-17
200.0
100.0
%
P2-17
Adjustable Threshold 1 Lower Limit (Analog Output 1
/ Relay Output 1)
0.0
P2-16
0.0
%
Used in conjunction with some settings of Parameters P2-11 & P2-15.
9
Extended P
arameters