5.3.1
Quick setup: Project AS-i networks
41782
During projection adaptation, the AS-i master carries out the following actions:
The configuration data of all detected AS-i slaves (LDS) is saved
The detected AS-i slaves are added to the list of projected slaves (LPS)
During a project a projection adaptation all output parameters of the unconnected AS-i slaves
are reset to their default value in the AS-i master (single /A slaves = 0xF, B slaves = 0x7).
To carry out the projection adaptation on AS-i master 1 and/or AS-i master 2:
1 Select menu page
►
►
Select tab [Project all].
2 Select the AS-i master for projection adaptation
►
Set the following parameters as required:
Parameter
Description
Possible values
[AS-i Master 1]
Select AS-i Master 1 for projection
adaptation
Exclude AS-i Master 1 from projection adaptation
Include AS-i Master 1 in projection adaptation
[AS-i Master 2]
Select AS-i Master 2 for projection
adaptation
(only available for devices with 2
AS-i masters)
Exclude AS-i Master 2 from projection adaptation
Include AS-i Master 2 in projection adaptation
3 Start the projection adaptation
►
Activate the button [Start projection process].
>
The selected AS-i masters go into the "projection mode".
>
A projection adaptation is carried out on the selected AS-i masters.
>
After projection adaptation, the selected AS-i masters go into the "protected mode".