SmartPLC DataLine with EtherNet/IP device interface
167
>
Example: structure of the digital input data
41498
Task:
The digital input data of slaves 1A, 3 and 6A of AS-i master 1 are to be transmitted.
Solution:
Slot: 1
Module configuration:
01 ... 07
Data length: 2 words
The following table shows in which positions of the two word sized data block the digital input data of
the slaves are transmitted:
Data block (2 words)
Bits
31...28
Bits
27...24
Bits
23...20
Bits
19...16
Bits
15...12
Bits
11...8
Bits
7...4
Bits
3...0
1A
3
6A
>
Table: Master flags
41665
Bits 12...15 of the first word of the digital input data contain the master flags. They provide information
on the operating state of the AS-i master. The following table shows the meaning of each bit:
Bit 15
Bit 14
Bit 13
Bit 12
AS-i power fail
(19 V)
Configuration error in the
AS-i circuit
AS-i master is offline
(AS-i data is invalid)
Periphery fault in the AS-i
circuit
Possible values per bit:
0 = no error
1 = error
In the digital output data, bits 12...15 have no relevance and are not evaluated!