SmartPLC DataLine with EtherNet/IP device interface
94
>
Set the EtherNet/IP module configuration
41646
NOTICE!
For the transmission of cyclic process data between the device and the EtherNet/IP PLC, a
limited number of data words is available for each direction of transmission:
Input data (= modules 1, 3, 5, 7, 9, 10, 13, 14): 248 words
Output data (= modules 2, 4, 6, 8, 11, 12, 15): 248 words
If the EtherNet/IP modules have been parameterised in such a way that the cyclic input and
output data comprise more than 248 words per direction of transmission, any data from the
249th word will not be transmitted and will therefore be lost.
>
Risk of data loss.
► Parameterise the EtherNet/IP modules in a way to ensure that the input and output data
do not exceed the maximum number of words to be transmitted.
The EtherNet/IP modules can only be configured on the device if the configuration mode is set
to
Independent
(
→
Set the configuration mode
(
)).
To define which cyclic process data are to be transmitted in the EtherNet/IP slots:
1 Select the menu page
►
>
>
►
Select [Module configuration] tab.
2 Set the EtherNet/IP slots for the digital inputs and outputs of the AS-i slaves
>
Set the following parameters as required:
Parameter
Description
Possible values
[EtherNet/IP: Slot 1]
Digital inputs of the S/A slaves
connected to AS-i master 1
→
Slot 1 – Digital input data single or A slaves, AS-i master 1
(
[EtherNet/IP: Slot 2]
Digital outputs of the S/A slaves
connected to AS-i master 1
→
Slot 2 – Digital output data single or A slaves, AS-i master 1
(
[EtherNet/IP: Slot 3]
Digital inputs of the S/A slaves
connected to AS-i master 2
(only devices with 2 AS-i masters)
→
Slot 3 – Digital input data single or A slaves, AS-i master 2
(
[EtherNet/IP: Slot 4]
Digital outputs of the S/A slaves
connected to AS-i master 2
(only devices with 2 AS-i masters)
→
Slot 4 – Digital output data single or A slaves, AS-i master 2
(
[EtherNet/IP: Slot 5]
Digital inputs of the B slaves
connected to AS-i master 1
→
Slot 5 – Digital input data B slaves, AS-i master 1
(
→ S.
[EtherNet/IP: Slot 6]
Digital outputs of the B slaves
connected to AS-i master 1
→
Slot 6 – Digital output data B slaves, AS-i master 1
(
→ S.
[EtherNet/IP: Slot 7]
Digital inputs of the B slaves
connected to AS-i master 2
(only devices with 2 AS-i masters)
→
Slot 7 – Digital input data B slaves, AS-i master 2
(
→ S.
[EtherNet/IP: Slot 8]
Digital outputs of the B slaves
connected to AS-i master 2
(only devices with 2 AS-i masters)
→
Slot 8 – Digital output data B slaves, AS-i master 2
(
→ S.
3 Set the EtherNet/IP slots for the analogue inputs and outputs of the AS-i slaves
►
Set the following parameters as required: