SmartPLC DataLine with EtherNet/IP device interface
92
>
Set the configuration mode
41650
More information:
→
Configuration mode
(
To set the configuration mode of the device:
1 Select the menu page
►
>
>
►
Select [Fieldbus] tab.
2 Select the configuration method for the EtherNet/IP parameters
>
Set the following parameter as required:
Parameter
Description
Possible values
[Configuration mode]
Active configuration mode of
the device
[Top-Down
]
The device-specific parameters and the module
configuration are set via the projection software
of the EtherNet/IP controller.
[
Independent]
The parameters of the EtherNet/IP interface are
set via the graphical user interface of the device.
3 Save the changes
>
Press [Accept] button.
>
Selected value is applied.
>
Set the device-specific parameters
41642
The parameters can only be changed if the configuration mode is set to
Independent
(
→
Set
the configuration mode
(
To set the device-specific parameters: set the number of channels to be transmitted per analogue
input slave:
1 Select the menu page
►
>
>
►
Select [Parameter] tab.
2 Set the number of analogue channels per input slave
►
Set the following parameter as required:
Parameter
Description
Possible values
[Analog. channels/I-slave]
Number of analogue
channels transmitted per
input slave
[1 channel per A/B]
1 channel per A/B slave
OR:
channels 1 + 3 per single slave
[1 channel]
1 channel per single slave
OR:
1 channel per A slave
[2 channels]
2 channels per single slave
OR:
2 channels per A slave
[4 channels]
4 channels per single slave
OR:
2 channels per A/B slave