Examples:
Command: $012
Response: !01320614
Reads the configuration of module 01 and the module
returns a response of 0 to 10V range, 9600 bps,
1V/second slew rate and engineering data format.
Command: #012+10.000
Response: >
Sets the output of channel 2 of the module 01 to
+10.000 and the module returns a valid response.
Command: $0162
Response: !01+10.000
Reads the last written analog output value of channel
2 of the module 01 and the module r10.000.
Command: $0182
Response: !01+01.000
Reads the current analog output value of channel 2 of
the module 01 and the module r01.000.
Related Commands:
Section 2.4 #AAN(Data), Section 2.17 $AA6N
Related Topics:
Section 1.11 Configuration Tables, Section A.6 Slew Rate
Control, Section A.7 Analog Output Read-back
Note:
This command is only applicable to the I-7022, I-7024,