2.3 #AAN
Description:
Reads the counter data of a specified digital input channel.
Syntax:
#AAN[CHKSUM](CR)
#
Delimiter character
AA
Address of the module to be read (00 to FF)
N
The channel to be read, zero based.
Response:
Valid Command:
!AA(Data)[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command. An
invalid command is returned if the specified
channel is incorrect.
AA
Address of the module in hexadecimal format
(00 to FF)
(Data)
Five digits data of the counter value of the
specified channel.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.