![ICP DAS USA M-7024 User Manual Download Page 40](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159040.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
40
Analog Output Configuration for I-7022, M-7022,
M-7204U and M-7028
Analog Output Type Setting (T)
Type Code
Output Range
0
0 mA ~ +20 mA
1
+4 mA ~ +20 mA
2
0 V ~ +10 V
3*
-10 V ~ +10 V
4*
0 V ~ +5 V
5*
-5 V ~ +5 V
Notes:
1.
The type code 4 is only available to M-7024U, M-7028 and
I-7022/M-7022 firmware version B1.2 and later.
2.
The type code 3 and 5 are only available to M-7024U and
M-7028.
Slew Rate Setting (S)
S
V/s
mA/s
0
Immediate
Immediate
1
0.0625
0.125
2
0.125
0.25
3
0.25
0.5
4
0.5
1.0
5
1.0
2.0
6
2.0
4.0
7
4.0
8.0
8
8.0
16.0
9
16.0
32.0
A
32.0
64.0
B
64.0
128.0
C
128.0
256.0
D
256.0
512.0
E
512.0
1024.0