![ICP DAS USA M-7024 User Manual Download Page 80](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159080.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
80
2.13 $AA4N
Description:
Sets the current output of a specified channel as the
power-on value.
Syntax:
$AA4N[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
4
Command to set the power on value
N
The channel to be set, zero based
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: #01100.000
Response: >
Sets the output of channel 1 of module 01 to
0.0mA and returns a valid response.
I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028
Summary of Contents for M-7024