![ICP DAS USA M-7024 User Manual Download Page 161](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159161.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
161
M-7022, M-7024, M-7024L, M-7024R, M-7024U
3.8 16 (0x10) Write Multiple Registers
This function code is used to write the analog output values of a
module.
Request
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x10
02 ~ 03 Starting channel 2 Bytes 0x0000 ~ 0x0001 for M-7022
0x0000 ~ 0x0003 for M-7024
0x0000 ~ 0x0003 for M-7024L
0x0000 ~ 0x0003 for M-7024R
0x0000 ~ 0x0003 for M-7024U
0x0000 ~ 0x0007 for M-7028
04 ~ 05 Number of
output channels
(N)
2 Bytes 0x0001 ~ 0x0002 for M-7022
0x0001 ~ 0x0004 for M-7024
0x0001 ~ 0x0004 for M-7024L
0x0001 ~ 0x0004 for M-7024R
0x0001 ~ 0x0004 for M-7024U
0x0001 ~ 0x0008 for M-7028
06
Byte count
1 Byte
Number of bytes of the following
output values, 2 x N
07
Data of output
channels
2 x N
Bytes
Data in the specified data format, 2
bytes for each channel
Response
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x10
02 ~ 03 Starting channel 2 Bytes The value is the same as byte 02 and
03 of the Request
04 ~ 05 Number of
output channels
2 Bytes The value is the same as byte 04 and
05 of the Request
Error Response
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x90
02
Exception code
1 Byte Refer to the Modbus standard for
more details.
Summary of Contents for M-7024
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...