I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
153
3. Modbus RTU Protocol
The Modbus protocol is developed by Modicon Inc., originally
developed for Modicon controllers. Detailed information can be
found at
http://www.modicon.com/techpubs/toc7.html
. You can
also visit
http://www.modbus.org
to find more valuable
information.
M-7000 series modules support the Modbus RTU protocol. The
communication Baud Rates range from 1200bps to 115200bps.
The number of data bits is fixed to 8. For M-7022 firmware
version B102 and later, M-7024 firmware version B202 and later,
M-7024L, M-7024R, M-7024U and M-7028, the parity can be
none, even or odd. For M-7022 other versions and M-7024 other
versions, the parity and stop bits are fixed as no parity and 1 stop
bit. The following Modbus functions are supported.
Function Code Description
Section
01 (0x01)
Read coils
3.1
02 (0x02)
Read digital inputs
3.2
03 (0x03)
Read output channels
3.3
04 (0x04)
Read input channels
3.4
05 (0x05)
Write single coil
3.5
06 (0x06)
Write single register
3.6
15 (0x0F)
Write multiple coils
3.7
16 (0x10)
Write multiple registers
3.8
If the function specified in the message is not supported, then the
module responds as follows.
Error Response
00
Address
1 Byte 1 to 247
01
Function code
1 Byte Function code | 0x80
02
Exception code 1 Byte 01
If a CRC mismatch occurs, the module will not respond.
Summary of Contents for M-7024
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...