I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
72
2.9 $AA2
Description:
Reads the module configuration.
Syntax:
$AA2[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
2
Command to read the module configuration
Response:
Valid Command:
!AATTCCFF[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
TT
Type code of the module. For the I-7022,
M-7022, M-7024U and M-7028, this field is to
3F and 00 for M-7024U and M-7028, see
Section 1.110 for details.
CC
Baud Rate code of the module, see Section 1.11
for details.
FF
Data format, checksum settings and slew rate
settings of the module, see Section 1.11 for
details.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
I-7021, I-7021P, I-7022, I-7024, I-7024R, M-7021A
M-7022, M-7022A, M-7024, M-7024L, M-7024R, M-7024U, M-7028
Summary of Contents for M-7024
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...