3.6 06 (0x06) Write Single Register
This function code is used to write a digital output value of a
module.
Request
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x06
02 ~ 03 Output channel
numbers
2 Bytes 0x0000 ~ 0x0001 for M-7022
0x0000 ~ 0x0003 for M-7024
0x0000 ~ 0x0003 for M-7024L
0x0000 ~ 0x0003 for M-7024R
0x0000 ~ 0x0003 for M-7024U
0x0000 ~ 0x0007 for M-7028
04 ~ 05 Output value
2 Bytes Data in the specified data format
Response
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x06
02 ~ 03 Output channel
numbers
2 Bytes The value is the same as byte 02 and
03 of the Request
04 ~ 05 Output value
2 Bytes The value is the same as byte 04 and
05 of the Request
Error Response
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x86
02
Exception code
1 Byte Refer to the Modbus standard for
more details.