![ICP DAS USA M-7024 User Manual Download Page 100](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159100.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
100
2.23 $AA9N
Description:
Reads the analog output configuration of a specified
channel.
Syntax:
$AA9N[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
9
Command to read the analog output
configuration
N
The channel to be read, zero based
Response
:
Valid command:
!AATS[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
T
Analog output type, see Section 1.11 for details.
S
Analog output slew rate, see Section 1.11 for
details.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
I-7022
M-7022, M-7024U, M-7028
Summary of Contents for M-7024
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...