2.31 $AAPN
Description:
Sets the communication protocol.
Syntax:
$AAPN[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
P
Command to set the communication protocol
N
0: DCON protocol
1: Modbus RTU protocol
Before using this command, the rear slide switch
must be in the INIT position for M-7024U and
M-7028, or the INIT * terminal should be
connected to the GND terminal for M-7022,
M-7024 and M-7024R, see Section A.1 for
details. The new protocol is saved in the
EEPROM and will be effective after the next
power on reset.
Response:
Valid Response:
!AA[CHKSUM](CR)
Invalid Response: ?AA[CHKSUM](CR)
!
Delimiter character for a valid response
?
Delimiter character for an invalid response
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.