I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
174
Address Description
Attribute
40492
Host watchdog timeout count, write 0
to clear
R/W
00225 ~
00232
10225 ~
10232
Status of current output open wire
R
00257
Protocol, 0: DCON, 1: Modbus
R/W
00260
Modbus host watchdog mode
0: same as I-7000
1: can use AO and DO command to clear
host watchdog timeout status
R/W
00261
1: enable, 0: disable host watchdog
R/W
00269
Modbus data format, 0: hex, 1:
engineering
R/W
00270
Host watch dog timeout status, write 1
to clear host watch dog timeout status
R/W
00272
Write 1 to load factory default
calibration parameters
W
00273
Reset status, 1: first read after
powered on, 0: not the first read after
powered on
R
Analog Output Types
Type Code
Range
Data Format
Minimum
Maximum
0
0 mA ~ +20 mA
Engineering
0
+20000
Hexadecimal
0000h
FFFFh
1
+4 mA ~+20 mA
Engineering
+4000
+20000
Hexadecimal
0000h
FFFFh
2
0V ~ +10 V
Engineering
0
+10000
Hexadecimal
0000h
FFFFh
3
+/-10 V
Engineering
-10000
+10000
Hexadecimal
8000h
7FFFh
4
0 V ~ +5 V
Engineering
0
+5000
Hexadecimal
0000h
FFFFh
5
+/-5 V
Engineering
-5000
+5000
Hexadecimal
8000h
7FFFh
Summary of Contents for M-7024
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...