![ICP DAS USA M-7024 User Manual Download Page 62](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159062.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
62
Examples for I-7022 and M-7022:
Command: $012
Response: !013F0600
Reads the configuration of module 01. It returns:
engineering data format.
Command: $0190
Response: !0110
Reads the configuration of analog output channel 0 of
module 01. It returns: output type 4 mA to 20 mA and
output changing immediately.
Command: #01005.000 Response: >
Sets channel 0 of module 01 to output 5 mA. The
module returns a valid response.
Command: #01025.000 Response: ?
Sets channel 0 of module 01 to output 25 mA. The
module returns an out of range response and the output
is set to 20 mA.
Examples for I-7024, I-7024R, M-7024, M-7024L
and M-7024R:
Command: $012
Response: !01300600
Reads the configuration of module 01. It returns:
output type 0 mA ~ 20 mA, engineering data format
and output changing immediately.
Command: #010+05.000
Response: >
Sets channel 0 of module 01 to output 5 mA. The
module returns a valid response.
Command: #010+25.000
Response: ?
Sets channel 0 of module 01 to output 25 mA. The
module returns an out of range response and the output
is set to 20 mA.
I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028
Summary of Contents for M-7024
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...