![ICP DAS USA M-7024 User Manual Download Page 70](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159070.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
70
2.8 $AA1N
Description:
I-7022/M-7022
Performs 20 mA
calibration
I-7024/I-7024R/M-7024/M-7024R
firmware version A2.9 and earlier
Performs 20 mA
or +10 V
calibration
M-7022A/M-7024L/M-7024U/
M-7028, I-7024/I-7024R/M-7024/
M-7024R firmware version A3.0
and later
Performs a span
calibration
Syntax:
$AA1N[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be calibrated (00 to FF)
1
Command for the 20 mA/+10 V/span calibration
N
Specifies the channel to be calibrated, zero based
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
I-7022, I-7024, I-7024R
M-7022, M-7022A, M-7024, M-7024L, M-7024R, M-7024U, M-7028
Summary of Contents for M-7024
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...