![ICP DAS USA M-7024 User Manual Download Page 105](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159105.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
105
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: $01B
Response: $0102
Diagnoses the analog outputs of module 01. The
module returns a valid response and channel 1 is
either wire opening for current output or short circuit
for voltage output.
Note:
This command is only applicable to the M-7024U and
M-7028.
M-7024U, M-7028