![ICP DAS USA M-7024 User Manual Download Page 102](http://html1.mh-extra.com/html/icp-das-usa/m-7024/m-7024_user-manual_614159102.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
102
2.24 $AA9NTS
Description:
Sets the analog output configuration of a specified channel.
Syntax:
$AA9NTS[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
9
Command to set the analog output configuration
N
The channel to be set, zero based
T
Analog output type, see Section 1.11 for details.
S
Analog output slew rate, see Section 1.11 for
details.
Response
:
Valid command:
!AA[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
I-7022
M-7022, M-7024U, M-7028