CAN-8x23 user’s manual (Revision 3.20, Ma r/08/2012) ------
190
I-87018 Series
Type 00 to 06 Definition
Range Code
(Hex)
Input Range
Data Format
Full Scale
Negative
Full Scale
00
-15mV to +15mV
Input Range
+15.000 mV
-15.000 mV
2's Complement HEX
7FFF
8000
01
-50mV to +50mV
Input Range
+50.000 mV
-50.000 mV
2's Complement HEX
7FFF
8000
02
-100mV to +100mV
Input Range
+100.00 mV
-100.00 mV
2's Complement HEX
7FFF
8000
03
-500mV to +500mV
Input Range
+500.00 mV
-500.00 mV
2's Complement HEX
7FFF
8000
04
-1V to +1V
Input Range
+1.0000 V
-1.0000 V
2's Complement HEX
7FFF
8000
05
(default)
-2.5V to +2.5V
Input Range
+2.5000 V
-2.5000 V
2's Complement HEX
7FFF
8000
06
*1
-20mA to +20mA
with 125
Ω
resistor
Input Range
+20.000 mA
-20.000 mA
2's Complement HEX
7FFF
8000
Note:
*1: When I-87018 and I-87018R are connecting to a current source set to 06 type code,
an optional external 125 Ohms resistor is required.