CAN-8x23 user’s manual (Revision 3.20, Ma r/08/2012) ------
15
2.5 Terminal Resistor Jumper and Initial Switch
The jumpers enable/disable of the terminal resistor show as follow:
Device
Jumper
Enable
Disable
CAN-8123 / CAN-8223
JP2
CAN-8423
JP1
CAN-8823
JP1
Before updating firmware or using the utility tool to configure the
CAN-8423 and the CAN-8823, the initial mode is needed. For more detail
configuration, please refer to the cheaper 4. Since the CAN-8123/CAN-8223
doesn
’t support RS-232 COM Port, the utility tool in the off-line mode takes the
place to get the EDS file.
Following shows the initial switch of CAN-8423 and CAN-8823
(CAN-8123/CAN-8223 not support the initial function)
.
Device
Switch
Initial Mode
Run Mode
CAN-8423
Baud
Rotary Switch
Switch to
“9”
Switch to
“0” ~ “7”
CAN-8823
SW1
Switch to
“Init”
Switch to
“Run”
2.6 Power LED
The CAN series products (CAN-8x23) need 10 to 30 VDC power supplies,
(Please note that other slot modules, inserted in, will also consume part of the
inputted power). Under a normal connection, a good power supply and a
correct voltage selection, as the unit is turned on, the LED will light up in yellow.
If it can’t work, please check with local agents or resellers for more help.
CANopen Status LED