CAN-8x23 user’s manual (Revision 3.20, Ma r/08/2012) ------
174
4
reversed
---
---
---
5
event timer
UNS IGNED 16
RW
0
1804h
0
largest sub-index supported for
“receive PDO parameter”
UNS IGNED 8
RO
5
1
COB-ID used by PDO (Tx)
UNS IGNED 32
RW
80000000h
2
transmission type
UNS IGNED 8
RW
FFh
3
inhibit time
UNS IGNED 16
RW
0
4
reversed
---
---
---
5
event timer
UNS IGNED 16
RW
0
...
...
...
...
...
...
181Fh
0
largest sub-index supported for
“receive PDO parameter”
UNS IGNED 8
RO
5
1
COB-ID used by PDO (Tx)
UNS IGNED 32
RW
80000000h
2
transmission type
UNS IGNED 8
RW
FFh
3
inhibit time
UNS IGNED 16
RW
0
4
reversed
---
---
---
5
event timer
UNS IGNED 16
RW
0
TxPDO Mapping Communication Entries
Idx
Sidx
Description
Ty pe
Attr
Default
1A00h
0h
largest sub-index supported for
“transmit PDO mapping”
UNS IGNED 8
RO
8
1h
read digital input 1h to 8h
UNS IGNED 8
RW
6000 0108h
2h
read digital input 9h to 10h
UNS IGNED 8
RW
6000 0208h
3h
read digital input 11h to 18h
UNS IGNED 8
RW
6000 0308h
4h
read digital input 19h to 20h
UNS IGNED 8
RW
6000 0408h
5h
read digital input 11h to 28h
UNS IGNED 8
RW
6000 0508h
6h
read digital input 19h to 30h
UNS IGNED 8
RW
6000 0608h
7h
read digital input 11h to 40h
UNS IGNED 8
RW
6000 0708h
8h
read digital input 19h to 48h
UNS IGNED 8
RW
6000 0808h
1A01h
0h
largest sub-index supported for
“transmit PDO mapping”
UNS IGNED 8
RO
4
1h
read analog input 1h
UNS IGNED 16
RW
6401 0110h
2h
read analog input 2h
UNS IGNED 16
RW
6401 0210h