Application Guide - NP900 Series
221 (504
)
A996A
operate on its set timer settings. Requirement for this scheme to work properly is that the
motor start detection current is set below of to be blocked overcurrent stage.
3.3.1.1
S
ETTINGS AND SIGNALS
Settings of the motor status monitor (MST) function are mostly shared with motor
protection functions in the motor module of the IED. In following table are shown the
functions which use these settings also.
Table 3.3.1.1-148 Settings of the MST function.
Name
Range
Step
Default
Prot.funcs. Description
Motor Start
0: DOL
1: StarDelta
2: Softstart
-
0:DOL
MST
Ist> (48)
Motor starting mode selection.
Direct On Line,
Star-Delta or soft
started application will be selectable
in future releases.
Motor In Scaled
0.1... 40.0xIn 0.1xIn -
MST
TM> (49M)
Ist> (48)
I< (37)
Im> (50M)
Motor nominal current scaled to per
unit. If in the CT settings “Object In”
is selected this value should be
1.00. If scale to CT nominal then
this value may vary.
Motor In A
0.1 ... 5000A 0.1A
-
MST
TM> (49M)
Ist> (48)
I< (37)
Im> (50M)
Motor nominal current in amperes.
Nominal starting
current
0.1…40.0XIn 0.1xIn 6.0 xIn
MST
TM> (49M)
Ist> (48)
Im> (50M)
Motors locked rotor current with
nominal voltage. This setting is used
for the automatic curve selection
and calculation. Also nominal
starting capacity calculation is made
with this value.
Nominal starting
current A
0.1 ... 5000A 0.1A
-
MST
TM> (49M)
Ist> (48)
Im> (50M)
Motors locked rotor current in
amperes.
Start detect
current
0.1…40.0xIn 0.1xIn 1.5 xIn
MST
Ist> (48)
Motor starting current detection
limit. When in DOL or Start delta
mode this setting defines the
starting situation when measured
current exceeds this and no load
current setting in 10 ms time.
Start detect
current A
0.1 ... 5000A 0.1A
-
MST
Ist> (48)
Motor starting current detection limit
in amperes.
Min locked rotor
current
0.1…40.0xIn 0.1xIn 3.5 xIn
MST
TM> (49M)
Ist> (48)
Im> (50M)
Minimum locked rotor current of the
motor. This setting defines the
current limit when in the automatic
curve selection and control only
short time constant (stall) is used if
this current is exceeded.
Min locked rotor
current A
0.1 ... 5000A 0.1A
-
MST
TM> (49M)
Ist> (48)
Im> (50M)
Minimum locked rotor current of the
motor. This setting defines the
current limit when in the automatic
curve selection and control only
short time constant (stall) is used if
this current is exceeded.