Application Guide - NP900 Series
16 (504
)
connector 1 to connector 2 and the
secondary currents starpoint is towards
line.
IL2 Polarity
0:-
1:Invert
-
0:-
IL2 (second current) measurement
channel polarity (direction) selection.
Default setting is that positive current flow
is from connector 3 to connector 4 and
the secondary currents starpoint is
towards line.
IL3 Polarity
0:-
1:Invert
-
0:-
IL3 (third current) measurement channel
polarity (direction) selection. Default
setting is that positive current flow is from
connector 5 to connector 6 and the
secondary currents starpoint is towards
line.
CT scaling factor P/S -
-
-
IED feedback value, this is the calculated
scaling factor for primary /secondary
current ratio
CT scaling factor
NOM
-
-
-
IED feedback value, this is the calculated
ratio in between of set primary and
nominal currents.
Ipu scaling primary
-
-
-
IED feedback value, scaling factor from
p.u. value to primary current.
Ipu scaling
secondary
-
-
-
IED feedback value, scaling factor from
p.u. value to secondary current.
Table 3.1.1.4-3 Settings of the residual I01 CT scaling in NP900.
Name
Range
Step
Default
Description
I01 CT primary
1…5000.0 A
0.1A
100.0A
Rated primary current of the CT in
amperes.
I01 CT secondary
0.2…10.0 A
0.1A
5.0A
Rated secondary current of the CT in
amperes.
I01 Polarity
0:-
1:Invert
-
0:-
I01 (coarse residual) measurement
channel polarity (direction) selection.
Default setting is that positive current flow
is from connector 7 to connector 8.
CT scaling factor P/S -
-
-
IED feedback value, this is the calculated
scaling factor for primary /secondary
current ratio
Table 3.1.1.4-4 Settings of the residual I02 CT scaling in NP900.
Name
Range
Step
Default
Description
I02 CT primary
1…5000.0 A
0.1A
100.0A
Rated primary current of the CT in
amperes.
I02 CT secondary
0.0001…10.0 A 0.0001A 5.0A
Rated secondary current of the CT in
amperes.
I02 Polarity
0:-
1:Invert
-
0:-
I02 (fine residual) measurement channel
polarity (direction) selection. Default
setting is that positive current flow is from
connector 9 to connector 10.
CT scaling factor P/S -
-
-
IED feedback value, this is the calculated
scaling factor for primary /secondary
current ratio