Application Guide - NP900 Series
161 (504
)
A996A
3.2.14.7
E
VENTS AND REGISTERS
The UV function generates events and registers from the status changes of start, trip and
blocked. To main event buffer is possible to select status “On” or “Off” messages. The UV
function offers four independent instances which events are segregated for each instance
operation.
In the function is available 12 last registers where the triggering event of the function
(start, trip or blocked) is recorded with time stamp and process data values.
Table 3.2.14.7-111. Event codes of the UV function instance 1 – 4.
In the register of the UV function is recorded start, trip or blocked “On” event process data.
In the table below is presented the structure of UV function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.14.7-112. Register content.
Date & Time
Event
code
Fault type
Pretrig
voltage
Fault
voltage
Prefault
voltage
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
5696-
5893
Descr.
A … A-B-C
Start
average
voltage
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
Alarm
Type
5696
89 UV1
0 Start ON
1
0
5697
89 UV1
1 Start OFF
0
0
5698
89 UV1
2 Trip ON
1
1
5699
89 UV1
3 Trip OFF
0
0
5700
89 UV1
4 Block ON
1
0
5701
89 UV1
5 Block OFF
0
0
5760
90 UV2
0 Start ON
1
0
5761
90 UV2
1 Start OFF
0
0
5762
90 UV2
2 Trip ON
1
1
5763
90 UV2
3 Trip OFF
0
0
5764
90 UV2
4 Block ON
1
0
5765
90 UV2
5 Block OFF
0
0
5824
91 UV3
0 Start ON
1
0
5825
91 UV3
1 Start OFF
0
0
5826
91 UV3
2 Trip ON
1
1
5827
91 UV3
3 Trip OFF
0
0
5828
91 UV3
4 Block ON
1
0
5829
91 UV3
5 Block OFF
0
0
5888
92 UV4
0 Start ON
1
0
5889
92 UV4
1 Start OFF
0
0
5890
92 UV4
2 Trip ON
1
1
5891
92 UV4
3 Trip OFF
0
0
5892
92 UV4
4 Block ON
1
0
5893
92 UV4
5 Block OFF
0
0