Application Guide - NP900 Series
394 (504
)
A996A
Name
Range
Step
Default
Description
SYN U conditions LL only
LL & LD
LL & DL
LL & DD
LL & LD & DL
LL & LD & DD
LL & DL & DD
Bypass
-
LL only
Allowed states of the supervised systems.
SYN U live >
0.10…120.00 %Un 0.01%Un 20%Un
Voltage limit of the live state
SYN U dead <
0.10…120.00 %Un 0.01%Un 20%Un
Voltage limit of the dead state
SYN U diff <
0.00…120.00 %Un 0.01%Un 2%Un
Maximum allowed voltage difference
between the systems.
SYN angle diff <
0.00…90.00 deg
0.01 deg 0.5 deg
Maximum allowed angle difference
between the systems.
SYN freq diff <
0.00…0.50 Hz
0.01 Hz
0.1 Hz
Maximum allowed frequency difference
between the systems.
NOTE! Remember to set a voltage channel (U3 or U4) into synchrocheck mode in the voltage
transformer settings (Measurements > VT Module).
1.1.1.15
E
VENTS AND REGISTERS
The synchrocheck function generates events and registers from the status changes like
syn ok, bypass and blocked. To main event buffer is possible to select status “On” or “Off”
messages. The synchrocheck function offers three independent instances which events
are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function is
recorded with time stamp and process data values.