Application Guide - NP900 Series
63 (504
)
A996A
Resetting characteristics can be set according to the application. Default setting is
delayed with 60 ms and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the
operating time during the release time, function will not trip if the input signal is not
activated again during the release time counting.
3.2.2.5
E
VENTS AND REGISTERS
The NOC function generates events and registers from the status changes of start, trip
and blocked. To main event buffer is possible to select status “On” or “Off” messages. The
NOC function offers four independent instances which events are segregated for each
instance operation.
In the function is available 12 last registers where the triggering event of the function
(start, trip or blocked) is recorded with time stamp and process data values.
Table 3.2.2.5-49. Event codes of the NOC function instances 1 – 4.
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
1280
20 NOC1
0 Start ON
1
1281
20 NOC1
1 Start OFF
0
1282
20 NOC1
2 Trip ON
1
1283
20 NOC1
3 Trip OFF
0
1284
20 NOC1
4 Block ON
1
1285
20 NOC1
5 Block OFF
0
1344
21 NOC2
0 Start ON
1
1345
21 NOC2
1 Start OFF
0
1346
21 NOC2
2 Trip ON
1
1347
21 NOC2
3 Trip OFF
0
1348
21 NOC2
4 Block ON
1
1349
21 NOC2
5 Block OFF
0
1408
22 NOC3
0 Start ON
1
1409
22 NOC3
1 Start OFF
0
1410
22 NOC3
2 Trip ON
1
1411
22 NOC3
3 Trip OFF
0
1412
22 NOC3
4 Block ON
1
1413
22 NOC3
5 Block OFF
0
1472
23 NOC4
0 Start ON
1
1473
23 NOC4
1 Start OFF
0
1474
23 NOC4
2 Trip ON
1
1475
23 NOC4
3 Trip OFF
0
1476
23 NOC4
4 Block ON
1
1477
23 NOC4
5 Block OFF
0
In the register of the NOC function is recorded start, trip or blocked “On” event process
data. In the table below is presented the structure of NOC function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.2.2.5-50. Register content.