Application Guide - NP900 Series
418 (504
)
A996A
AR3 Request On
When autorecloser is executing shot requested by AR3 priority this signal is
activated. Signal can be connected to any relay IO as well as into communication
protocols.
AR4 Request On
When autorecloser is executing shot requested by AR4 priority this signal is
activated. Signal can be connected to any relay IO as well as into communication
protocols.
AR5 Request On
When autorecloser is executing shot requested by AR5 priority this signal is
activated. Signal can be connected to any relay IO as well as into communication
protocols.
Shot1 Running
When autorecloser is executing Shot1 this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
Shot2 Running
When autorecloser is executing Shot2 this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
Shot3 Running
When autorecloser is executing Shot3 this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
Shot4 Running
When autorecloser is executing Shot4 this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
Shot5 Running
When autorecloser is executing Shot5 this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
Final Trip
When autorecloser has executed Final Trip command this signal is activated.
Signal can be connected to any relay IO as well as into communication protocols.
AR Locked
When autorecloser is Locked mode this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
AR Inhibit
When autorecloser is in Inhibit mode this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
AR Lockout delay On
When autorecloser is calculating Lockout delay this signal is activated. Signal can
be connected to any relay IO as well as into communication protocols.
AR Arcing time On
When autorecloser is calculating Arcing time this signal is activated. Signal can be
connected to any relay IO as well as into communication protocols.
AR Reclaim time On
When autorecloser is calculating Reclaim time this signal is activated. Signal can
be connected to any relay IO as well as into communication protocols.
Status change of the output signals will always cause recorded event also in the AR
registers and AR continuous status indications. Events can be enabled or disabled
according to the application requirements.
3.6.4.14
S
ETTING PARAMETERS
Autorecloser function has freely configurable settings for all areas of the function in order
to control the operation of the autoreclosing application to suit different kind of needs.
Operation of the autorecloser can be static or dynamic based into if setting groups are
used. In autorecloser are found basic settings and shot related settings. Basic settings
control the desired Object selection as well as general behavior of the autorecloser in
different operating schemes.