Application Guide - NP900 Series
310 (504
)
A996A
HV side lead or
lag LV
0:Lead
1:Lag
-
0:Lead
TRF, DIFF Selection for HV side leads or
lags LV side. Selection is
visible only if vector group is
set to “0:Manual set”
LV side Star or
Zigzag / Delta
0:Star/Zigzag
1:Delta
-
0:Star/Zi
gzag
TRF, DIFF Selection of the LV side
connection, star or zigzag or
delta. Selection is visible only
if vector group is set to
“0:Manual set”
LV side grounded 0:Not
grounded
1:Grounded
-
0:Not
grounded
TRF, DIFF Selection whether the zero
sequence compensation
should be applied into LV side
currents calculation. Selection
is visible only if vector group is
set to “0:Manual set”
LV side lead or
lag HV
0:Lead
1:Lag
-
0:Lead
TRF, DIFF Selection for LV side leads or
lags LV side. Selection is
visible only if vector group is
set to “0:Manual set”
HV-LV side phase
angle
0.0…
360.00 deg
0.1deg
0.0deg
TRF, DIFF Angle correction factor for HV
LV sides, looked from HV side.
e.g. if transformer is Dy1 then
set here 30 degrees. Selection
is visible only if vector group is
set to “0:Manual set”
HV-LV side mag
correction
0.0…
100.0xIn
0.1xIn
0.0xIn
TRF, DIFF Magnitude correction for HV-
LV side currents per unitizing if
the currents are not directly
matched via calculation of the
nominal values. Selection is
visible only if vector group is
set to “0:Manual set”
Check online HV-
LV configuration
0:-
1:Check
-
0:-
TRF, DIFF Check online on energized
trafo the configuration
success. (Trafo needs to have
current flowing on both sides
as well as there should not be
faults seen in order this to
work). Selection is visible only
if vector group is set to
“0:Manual set”