Application Guide - NP900 Series
378 (504
)
A996A
Syncrocheck
permission
DI1 … DIx
(SWx)
Link to the physical binary input or synchrocheck function.“1” means that the
synchrocheck conditions are met and object can be closed. Position indication
can be done among binary inputs and protection stage signals by using IEC-
61850, GOOSE or logical signals.
Open Block
Input
DI1 … DIx
(SWx)
Link to the physical or software binary input.“1” means that the opening of the
object is blocked. Position indication can be done among binary inputs and
protection stage signals by using IEC-61850, GOOSE or logical signals.
Close Block
Input
DI1 … DIx
(SWx)
Link to the physical or software binary input.“1” means that the closing of the
object is blocked. Position indication can be done among binary inputs and
protection stage signals by using IEC-61850, GOOSE or logical signals.
LOC / REM
Pre-assigned
IED Local / Remote switch status. Control of the object has to be applied in the
correct control location. In local status remote controls cannot override the open
or close commands.
Status change of the monitor signals will always cause recorded event also in the object
registers and object continuous status indications. Events can be enabled or disabled
according to the application requirements.
Table 3.6.2.1-235 Command digital signal inputs used by the OBJ function.
Signal
Range
Description
Objectx Local
Close control
input
DI1 … DIx
Local Close command from physical digital input for example from pushbutton.
Objectx Local
Open control
input
DI1 … DIx
Local Open command from physical digital input for example from pushbutton.
Objectx
Remote Close
control input
DI1 … DIx
Remote Close command from physical digital input for example from RTU.
Objectx
Remote Open
control input
DI1 … DIx
Remote Open command from physical digital input for example from RTU.
Objectx
Remote Close
Signal
Pre-assigned Remote Close signal from communication protocols.
Objectx
Remote Open
Signal
Pre-assigned Remote Open signal from communication protocols.
Objectx Local
Close Signal
Pre-assigned Local Close signal from HMI, either select-execute from the mimic SLD or direct
from the local panel pushbutton.
Objectx Local
Open Signal
Pre-assigned Local Open signal from HMI either select-execute from the mimic SLD or direct
from the local panel pushbutton..
SW Open Input Configuration
assigned
Software controlled open signal. Can be from autoreclosing or user logic.
SW Close
Input
Configuration
assigned
Software controlled open signal. Can be from autoreclosing, synchroswitch or user
logic.
Command signal activations are logged in the function registers when applied. The
activation is logged also if the control is failed for any reason.