Application Guide - NP900 Series
102 (504
)
A996A
Table 3.2.8.1-74 Analogic magnitudes used by the HOC function.
Signal
Description
Time base
IL1FFT
Magnitudes (rms) of phase L1/A current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
IL2FFT
Magnitudes (rms) of phase L2/B current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
IL3FFT
Magnitudes (rms) of phase L3/C current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
I01FFT
Magnitudes (rms) of residual I01 current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
I02FFT
Magnitudes (rms) of residual I02 current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
Selection of the used AI channel and monitored harmonic as well as per unit monitoring or
percentage of fundamental monitoring is made with a setting parameter. In all possible
input channel variations pre-fault condition is presented with 20 ms averaged history value
from -20 ms of Start or Trip event.