Application Guide - NP900 Series
62 (504
)
A996A
mentioned here.
Delay
characteristics
IEEE
ANSI NI
ANSI VI
ANSI EI
ANSI LI
IEEE MI
IEEE VI
IEEE EI
Param
-
LTI
Setting is active and visible when Delay
Type is selected to IDMT.
IEEE and ANSI standard delay
characteristics. ANSI: Normal Inverse,
Very Inverse, Extremely inverse, Long
time inverse characteristics. IEEE:
Moderately Inverse, Very Inverse,
Extremely Inverse characteristics. Param
selection allows the tuning of the
constants A, B and C which allows setting
of characteristics following the same
formula as the IEEE curves mentioned
here.
Non-standard
characteristic
RI-type
RD-type
-
RI-type
Selection of the non-standard
characteristic. See the formulas from
chapter 3.2.1. General properties of a
protection function.
Time dial setting k 0.01…25.00 s
0.01 s
0.05 s
Setting is active and visible when Delay
Type is selected to IDMT or non-standard
characteristic.
Time dial / multiplier setting for IDMT
characteristics or non-standard
characteristic.
A
0.0000…250.0000
0.0001
0.0860
Setting is active and visible when Delay
Type is selected to IDMT.
Constant A for IEC/IEEE characteristics.
B
0.0000…5.0000
0.0001
0.1850
Setting is active and visible when Delay
Type is selected to IDMT.
Constant B for IEC/IEEE characteristics.
C
0.0000…250.0000
0.0001
0.0200
Setting is active and visible when Delay
Type is selected to IDMT.
Constant C for IEEE characteristics.
Table 3.2.2.4-48 Reset time characteristics setting parameters.
Release Time
delay
0.000…150.000 s
0.005 s
0.06 s
Resetting time. Time allowed in between
of pick-ups if the pick-up has not lead into
trip operation. During this time the start
signal is held on for the timers if delayed
pick-up release is active.
Delayed Pick-up
release
No
Yes
-
Yes
Resetting characteristics selection either
time delayed or instant after pick-up
element is released. If activated the start
signal is reset after set release time delay.
Time calc reset
after release time
No
Yes
-
Yes
Operating timer resetting characteristics
selection. When active the operating time
counter is reset after set release time if
pick-up element is not activated during this
time. When disabled the operating time
counter is reset directly after the pick-up
element reset.
Continue time
calculation during
release time
No
Yes
-
No
Time calculation characteristics selection.
If activated the operating time counter is
continuing until set release time even the
pick-up element is reset.