Application Guide - NP900 Series
255 (504
)
A996A
Table 3.3.2.7-161. Event codes of the TOLM function instance
In the register of the TOLM function is recorded activated, blocked etc. “On” event process
data. In the table below is presented the structure of TOLM function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 3.3.2.7-162. Register content.
Date & Time
Event
code
Time to
reach 100%
theta
Ref. T
current
Active
meas
current
T at the
moment
Max
temp
rise
allowed
Temp
rise at
the
moment
Hot Spot
estimate
Hot
spot
max
all.
Trip
delay
rem
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
4288-
4297
Descr.
seconds
xIn
xIn
%
deg
deg
deg
deg
s
1 – 8
3.3.3
M
OTOR START
/
LOCKED ROTOR MONITORING
(LRC)
I
ST
>
(48,
14)
Motor start/locked rotor monitoring function (LRC) is used for monitoring the startup
duration and also the startup stress of the motor. LCR protection function can also be
used after starting for locked rotor protection.
Operating principle of the LCR function is either definite maximum locked rotor time
monitoring or inverse operating time based into allowed I
2
t calculation. When using I
2
t
calculation given start up timing the maximum allowed starting time is automatically scaled
according to the motor current and for example it is giving longer starting time for the
motor if the network voltage is lower and thus the starting current is lower, the motor start-
up will take longer time also. Maximum allowed starting time can be set manually or the
function can be set to follow motor manufacturer given hot and cold safe stalling times
automatically. This requires that the thermal overload (TOLM) function is activated and set
up for the automatic safe stalling times to be picked and the thermal status of the motor to
be known for the LCR function. In addition to the settable allowed starting time also speed
switch input can be set for the function. Speed switch may be required in some high mass
Event
Number
Event
channel
Event block name
Event
Code
Description
4288
67 TOLF1
0 Alarm1 On
4289
67 TOLF1
1 Alarm1 Off
4290
67 TOLF1
2 Alarm2 On
4291
67 TOLF1
3 Alarm2 Off
4292
67 TOLF1
4 Inhibit On
4293
67 TOLF1
5 Inhibit Off
4294
67 TOLF1
6 Trip On
4295
67 TOLF1
7 Trip Off
4296
67 TOLF1
8 Block On
4297
67 TOLF1
9 Block Off