3.
To restore the new fcsx device to the correct vfchost, enter the
vfcmap
command as follows:
vfcmap -vadapter vfchost0 -fcp fcs0
4.
To check the vfchost mapping, enter the
lsmap
command as follows:
lsmap -vadapter vfchost2 -npiv
The output might look like the following example:
Name
Physloc
ClntID
ClntName
ClntOS
--------------- ---------------------------------------- ------- ---------- ------
vfchost2
U7895.42X.9999999-V1-C33
4
Status
NOT_LOGGED_IN
FC name
fcs0
FC loc code:U78AF.001.newSN99-P1-C35-L1-T1
Ports logged in 0
Flags
4<NOT_LOGGED>
VFC client name
VFC client DRC
In this example, the new serial number is represented as
newSN99
.
Recovering the system firmware
The system firmware is contained in separate temporary and permanent images in the flash memory of
the compute node. These images are referred to as TEMP and PERM, respectively. The compute node
normally starts from the TEMP image, and uses the PERM image as a backup. If the TEMP image
becomes damaged, such as from a power failure during a firmware update, you can recover the TEMP
image from the PERM image.
About this task
If your system hangs, start the PERM image. See “Starting the PERM image.”
Starting the PERM image
You can force the compute node to start the permanent (PERM) image.
About this task
To force the compute node to start the PERM image, see http://publib.boulder.ibm.com/infocenter/
flexsys/information/topic/com.ibm.acc.psm.hosts.doc/dpsm_managing_hosts_power_firmware.html.
Starting the TEMP image
The system firmware is contained in separate temporary and permanent images in the flash memory of
the compute node. These images are referred to as TEMP and PERM, respectively. The compute node
normally starts from the TEMP image. Start the TEMP image before you update the firmware.
480
Power Systems: IBM Flex System p270 Compute Node Installation and Service Guide
Summary of Contents for Flex System p270 Compute Node
Page 1: ...Power Systems IBM Flex System p270 Compute Node Installation and Service Guide IBM ...
Page 2: ......
Page 3: ...Power Systems IBM Flex System p270 Compute Node Installation and Service Guide IBM ...
Page 38: ...26 Power Systems IBM Flex System p270 Compute Node Installation and Service Guide ...
Page 40: ...28 Power Systems IBM Flex System p270 Compute Node Installation and Service Guide ...
Page 110: ...98 Power Systems IBM Flex System p270 Compute Node Installation and Service Guide ...
Page 498: ...486 Power Systems IBM Flex System p270 Compute Node Installation and Service Guide ...
Page 509: ...Appendix Notices 497 ...
Page 510: ...IBM Printed in USA ...