Hot-swap power supply
installation/removal
Danger
Overloading an electrical circuit breaker is potentially a
fire hazard and a shock hazard under certain
conditions. To avoid these hazards, adhere to the
instructions in the following statements.
1. If you are connecting to a 100–127 V AC power
source, connect each power cord to a separate
branch circuit.
2. If you are connecting to a 200–240 V AC power
source and the branch circuit breaker rating is:
a. 13 amps or less, connect each power cord
to a separate branch circuit.
b. 14 amps to 19 amps, do not connect more
than two power cords to the same branch
circuit.
c. 20 amps or greater, you may connect up to
three power cords to the same branch
circuit.
The server comes with three power supplies, three 220 V
AC power cords, and three 110 V AC power cords (U.S.
only). Be sure to select the appropriate power cord
voltage for the server environment. All three power cords
must have the same voltage.
If you connect the three:
220 V AC power cords to the power supplies, the
three power supplies support redundancy and
hot-swap capability.
110 V AC power cords to the power supplies, the
three power supplies do not support redundancy if the
system configuration exceeds any of these conditions:
–
More than six processors
–
More than 24 memory DIMMs
–
More than eight PCI adapters
For servers with redundant power, the loss of a single
power supply will not affect the server operation. Replace
a power supply that has failed as soon as convenient to
help maintain the redundant power and cooling capability.
When the AC power LED is on, the DC power LED is on,
and the System Power light on the operator panel is on,
the power supply has failed. See “Hot-swap Power
supplies” on page 80 for the location of the DC power
LEDs. See “Power supply LED errors” on page 173 for
more information on the DC power LEDs.
92
Netfinity Server HMM
Summary of Contents for 8500R - Netfinity - 8681
Page 2: ......
Page 8: ...vi Netfinity Server HMM...
Page 25: ...1 LVD low voltage differential Netfinity 8500R Type 8681 17...
Page 62: ...Caution Use safe practices when lifting 54 Netfinity Server HMM...
Page 242: ...I O Housing Assembly 1 2 3 4 5 6 7 234 Netfinity Server HMM...
Page 261: ...Related service information 253...
Page 262: ...254 Netfinity Server HMM...
Page 263: ...Related service information 255...
Page 264: ...256 Netfinity Server HMM...
Page 265: ...Related service information 257...
Page 278: ...270 Netfinity Server HMM...
Page 279: ...Related service information 271...
Page 280: ...272 Netfinity Server HMM...
Page 290: ...IBM Part Number 37L5123 Printed in U S A S37L 5123...