Chapter 8 Parameter
POWER CON
PCON-CB/LC
185
[6] Default velocity (Parameter No.8)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
8 Default velocity
VCMD
mm/s
(deg/s)
1 to Actuator’s
max. verocity
Rated actuator
speed
The factory setting is the rated velocity of the actuator.
When a target position is set in an unregistered position table, the setting in this parameter is
automatically written in the applicable position number.
It is convenient to set the velocity often used.
[7] Default acceleration/deceleration (Parameter No.9)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
9 Default acceleration/deceleration
ACMD
G
0.01 to actuator's
max. acceleration/
deceleration
Rated actuator's
acceleration/
deceleration
The factory setting is the rated acceleration/deceleration of the actuator.
When a target position is set in an unregistered position table, the setting in this parameter is
automatically written in the applicable position number.
It is convenient to set the acceleration/deceleration often used.
[8] Default positioning width (in-position) (Parameter No.10)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
10 Default positioning width
INP
mm
(deg) 0.01
(Note 1)
to 999.99
0.10
When a target position is set in an unregistered position table, the setting in this parameter is
automatically written in the applicable position number. When the remaining moving distance
enters into this width, the positioning complete signal PEND/INP is output.
It is convenient to set the positioning width often used.
Note 1 For RCP2, RCP3, RCP4, RCP5 Series actuators, it is down to the minimum positioning
width (L = Lead length/800 (encoder pulse value)).
[9] Current-limiting value at standstill during positioning (Parameter No.12)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
12 Current-limiting value at standstill
during positioning
SPOW
%
1 to 70
In accordance
with actuator
When the value is increased, the stop holding torque is increased.
Even though it is generally unnecessary to change this setting, setting the value larger is
necessary in the case a large external force is applied during stop. Please contact IAI.
Summary of Contents for PCON-CB series
Page 2: ......
Page 4: ...POWER CON PCON CB LC ...
Page 14: ...POWER CON PCON CB LC ...
Page 32: ...POWER CON PCON CB LC 18 ...
Page 84: ...Chapter 2 Wiring POWER CON PCON CB LC 70 ...
Page 174: ...Chapter 4 Field Network POWER CON PCON CB LC 160 7 EtherCAT Type 8 PROFINET IO Type ...
Page 190: ...Chapter 7 Absolute Reset and Absolute Battery POWER CON PCON CB LC 176 ...
Page 226: ...Chapter 8 Parameter POWER CON PCON CB LC 212 ...
Page 330: ...Chapter 10 Appendix POWER CON PCON CB LC 316 ...
Page 334: ......
Page 335: ......