Chapter 7
Absolute Reset and
Absolute Battery
POWER CON
PCON-CB/LC
173
(Example) From Monday to Friday ; charge for 8 hours per day, discharge for 16 hours,
Saturday and Sunday ; use with discharge
1) If the upper limit setting for the number of encoder revolution is 800 [PRM];
Full charge amount
: 24 [h] *5 [day]
= 120 [h]
Total charge amount : 8 [h] *1.6 [h] *5 [day] = 64 [h]
Total discharge amount : 16 [h] *5 [day] + 48 [h] = 128 [h]
→
Assuming a start with full charge on Monday, it is necessary to fully charge the battery
every 10 days.
2) If the upper limit setting for the number of encoder revolution is 400 [PRM];
Total charge amount : 8 [h] *3.3 [h] *5 [day] = 132 [h]
Total discharge amount : 16 [h] *5 [day] + 48 [h] = 128 [h]
→
It is not necessary to have a continuous full charge if starting on Monday.
4-hour charge is stored every week. The upper limit is the reference value for the
retaining duration after fully charged.
7.2.3 Absolute Battery Voltage Drop Detection
Error detection (Alarm Output *ALM
(Note 1)
Signal gets turned off starts to be conducted when the
voltage of the absolute battery gets low.
Note 1 *ALM are the signals of active low.
After the power is supplied to the controller, they are usually on and turned OFF when
an error is detected.
If the alarm is generated, it will be necessary to absolute reset after the battery
replacement.
Summary of Contents for PCON-CB series
Page 2: ......
Page 4: ...POWER CON PCON CB LC ...
Page 14: ...POWER CON PCON CB LC ...
Page 32: ...POWER CON PCON CB LC 18 ...
Page 84: ...Chapter 2 Wiring POWER CON PCON CB LC 70 ...
Page 174: ...Chapter 4 Field Network POWER CON PCON CB LC 160 7 EtherCAT Type 8 PROFINET IO Type ...
Page 190: ...Chapter 7 Absolute Reset and Absolute Battery POWER CON PCON CB LC 176 ...
Page 226: ...Chapter 8 Parameter POWER CON PCON CB LC 212 ...
Page 330: ...Chapter 10 Appendix POWER CON PCON CB LC 316 ...
Page 334: ......
Page 335: ......