Chapter 3 Operation
POWER CON
PCON-CB/LC
137
[5] Pause and Operation Interruption (ST*, *STP, RES, PE*, PEND)
Turning start signal ST* OFF allows the actuator to be paused while it is moved. To restart it,
turn the same ST* signal ON.
Control method
If start signal ST* is turned OFF during movement, the actuator can be paused.
Use the control method for interlock in case where an object is invaded into the moving
direction of the actuator being moved.
1) If the ST* signal is turned OFF during movement, the actuator is decelerated to a stop. The
deceleration is the value set in the position table.
2) If the ST* signal is turned ON again, the remaining movement is continued. The
acceleration is the value set in the position table.
Before operation
Positioning
complete
state
Operation
Temp.
stop
Cont.
Op.
Position
complete
Velocity
Operation of actuator
Start signal
ST*
(
PLC
→
Controller)
LS* not
turned ON
Position sensing Output
LS*
(Controller
→
PLC)
Summary of Contents for PCON-CB series
Page 2: ......
Page 4: ...POWER CON PCON CB LC ...
Page 14: ...POWER CON PCON CB LC ...
Page 32: ...POWER CON PCON CB LC 18 ...
Page 84: ...Chapter 2 Wiring POWER CON PCON CB LC 70 ...
Page 174: ...Chapter 4 Field Network POWER CON PCON CB LC 160 7 EtherCAT Type 8 PROFINET IO Type ...
Page 190: ...Chapter 7 Absolute Reset and Absolute Battery POWER CON PCON CB LC 176 ...
Page 226: ...Chapter 8 Parameter POWER CON PCON CB LC 212 ...
Page 330: ...Chapter 10 Appendix POWER CON PCON CB LC 316 ...
Page 334: ......
Page 335: ......