HydraSwing Wiring Chart (Incoming Power)
The maximum distance shown is from the operator to the power source, assuming that source power is from a
panel box with adequate capacity to support the addition of this motor load. The values are for one operator,
with no other loads applied to the branch circuit. Avoid placing more than one operator to a circuit, but if you
must, be certain to reduce the maximum allowed wire distance by half.
NOTE:
HydraSwing gate operators connected for 1Ø operation will draw more current because the utility power to run the
machine will be carried to the operator on two wires instead of the three used for 3Ø operators. Be sure to allow for this difference
when specifying wire size.
Make sure proper wiring is being used. The following table shows the maximum allowable wire run from the
power source to the operator for various wire sizes. Performance of VFD operators on 1Ø and 3Ø 50\60 Hz
Power.
NOTE:
Distance shown in U.S. Standard “feet.” Metric equivalent shown in parentheses.
Phase Ø
1
1
3
3
3
3
Voltage
208
230
208
230
380
460
Horsepower
2
2
2
2
2
2
VFD Rating
Amps
17.4
17.4
8.7
8.7
5.2
5.2
Wire Gauge
Distance
Distance
Distance
Distance
Distance
Distance
12
90 (27m)
100 (30m)
220 (67m)
240 (73m)
680 (207m)
830 (253m)
10
150 (46m)
170 (52m)
350 (107m)
390 (119m)
1090 (332m)
1310 (399m)
8
240 (73m)
270 (82m)
560 (171m)
620 (189m)
1730 (527m)
2100 (640m)
6
390 (119m)
430 (131m)
900 (274m)
990 (302m)
2750 (838m)
3330 (1015m)
4
620 (189m)
680 (207m)
1430 (436m)
1580 (482m)
4380 (1335m)
5300 (1615m)
2
990 (302m)
1090 (332m)
2280 (695m)
2530 (771m)
6990 (2130m)
8470 (2582m)
Performance of Operators on 1 and 3 Phase 50/60Hz
A HySecurity Variable Speed Drive (VFD) operators can operate on a wide variety of incoming power.
• 50Hz/60Hz operation with no changes or reconnection
•
1Ø or 3Ø operation by field rewiring and reconnection. The incoming voltage must match the operator
nameplate. Although the electric motor can be reconnected, a different VFD (motor controller inside
the grey control box) is required between 460V and 208V/230V.
• Any AC powered peripherals such as locks, card readers and other devices need to be checked for
compatibility.
• The electric motors in all variable frequency drive operators are 3Ø/60Hz motors and are connected
for the voltage on the operator nameplate. (208V/230V or 460V)
How is this done?
18
MX3636-01 Rev. D
HydraSwing Programming & Operations
© 2018
Summary of Contents for HSG80F
Page 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Page 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Page 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...