64
MX3654-01 Rev. D
HydraSwing Programming & Operations
© 2018
Setting
Performance
Description
Wire
Connection
7
Gate forced open output
Activated if the gate is forced off the closed limit switch and
the operator is not able to restore the gate to full closed
position within four seconds.
NOTE:
This alarm resets itself in 30 seconds.
Relay 1, 2 or 3
8
Gate open too long output
Controls an external device. Activates when the gate is open
longer than the user-selected period of time. Adjustable
from 0 seconds with 15 to 135s selectable delay timeframes
in 30s increments.
NOTE:
TL - Open TIME ALERT adjustments can be made
in the Installer Menu. The TL Installer Menu display only
appears when using this relay.
Relay 1, 2 or 3
9
Safety Mode Alert output
Controls an external device. Activated when the system is
in Safety Mode or Entrapment Mode. Safety Mode occurs
when the gate encounters an obstruction. Entrapment
Mode means the gate is stopped. Entrapment mode occurs
if the inherent entrapment sensor triggers while the system is
in Safety Mode.
Relay 1, 2 or 3
10
Entrapment Mode Alert output
Controls an external device. Activated only when in the
Entrapment Mode.
Relay 1, 2 or 3
11
Unauthorized Vehicle Entry output
(Tailgate alert)
Controls an external device. Activated when a second vehicle
enters from the outside without a valid input from an access
control device. This output releases when an access control
input signals open or the arm/gate reaches the close limit.
Relay 1, 2 or 3
12
Outside Obstruction Vehicle
Detector output
Interlocks an entry device to prevent pedestrian use. This
output is active whenever the Outside Obstruction Loop
Detector is tripped.
Relay 1, 2 or 3
13
Loitering Alert
Indicates a vehicle is loitering on the Outside Obstruction
Loop. Adjustable from 0 seconds with 15 to 135s selectable
delay timeframes in 30s increments.
NOTE:
LT
LOITERING ALERT adjustments can be made
in the Installer Menu. The LT Installer Menu display only
appears when using this relay.
Relay 1, 2 or 3
14
Gate nearing full travel output
(Nearing Limit)
Applies to operators with position sensors only. Activated
when the gate is 3s from expected limit switch trigger.
NOTE:
If the operator has not yet learned limits, it will
energize Relay 14 when the motor begins moving the gate.
Relay 1, 2 or 3
15
Gate failure output
(Fault mode alert)
Activated to report occurrence of a problem. Indicates
the system is in an Error Mode, Fault Mode or Entrapment
Mode.
Relay 1, 2 or 3
16
Motor Running output
Active when the motor is running and gate is in motion.
Relay 1, 2 or 3
17
AC Power Failure output
This relay is normally energized and drops with loss of AC
power.
Relay 1, 2 or 3
18
DC Power Failure output
(Low battery alert)
DC operators only.
The relay activates when the battery
power is very low, but the output ceases when the battery is
dead. The relay is triggered when the battery is less than 20
volts.
Relay 1, 2 or 3
19
Flasher Relay
Flashes lights once per second. The relay is constantly
pulsing except when the open limit switch is triggered.
* Preferred connection is Relay 3, a solid state relay (except
on Crash). On Crash gate operators, Relay 3 is unavailable
because it is hard-wired for the LED barrier arm lights.
Relay 1 or 2*
(Relay 3)
Summary of Contents for HSG80F
Page 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Page 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Page 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...